retention basin steel for 1-2 200 l drums
L: 1200, W: 800, H: 360 (mm)|Article code: 40WM2
Smart choice
Price per item
(excl. shipping costs)
:
€ 407,95
€ 509,94 inc. VAT
Quantity
Your transport advantage
-28%
Order 6 more get
Order 6 more get
26 October delivered
Free pick up in Wapenveld
Specifications
Dimensions & Weight
Length (mm)
1200
Width (mm)
800
Height (mm)
360
Weight (kg)
72
Capacity & Load Bearing
Collection volume (ltr)
243
Materials & Construction
Material
steel
Walls
flat steel plate 3 mm
Floor
with galvanized grid
Top
1000kg/m2
Colour
grey
Surface treatment
galvanized
Functionality & Features
Type
Retention Basin
Implementation
for 1-2 200 l drums
Additional specifications
StawaR approved (DE)
Product Details
Article code:
40WM2
Article arrangement
New
EAN Code (Gtin):
8719424007619
Description
Steel drip tray suitable for two 200 liter drums. The capacity of this container is 243 litres. The drip tray and grid are made of hot-dip galvanized steel.
Guideline for storage and temporary storage for drip trays with regard to fire safety, occupational safety and environmental safety according to PGS 15 (publication series hazardous substances):
A storage facility must be constructed in such a way that leaked or spilled hazardous liquid is collected in a container. To this end, the collection container must have a capacity of at least 110% of the largest package. However, if 10% of the total content of the packages is more than 110% of the content of the largest package, then the collection capacity must be equal to 10% of the total content of the packages together. The collection container must be sufficiently resistant to the stored liquids.
The collection capacity only applies to liquids. Empty, uncleaned packaging does not count. The collection facility may also be realized in storage. The choice of location for the collection facility may depend on the hazardous liquids stored. Kruizinga.nl is not liable for the type of use!
Please note! Any form of modification is not allowed. If this is the case, all regulations will lapse.
Guideline for storage and temporary storage for drip trays with regard to fire safety, occupational safety and environmental safety according to PGS 15 (publication series hazardous substances):
A storage facility must be constructed in such a way that leaked or spilled hazardous liquid is collected in a container. To this end, the collection container must have a capacity of at least 110% of the largest package. However, if 10% of the total content of the packages is more than 110% of the content of the largest package, then the collection capacity must be equal to 10% of the total content of the packages together. The collection container must be sufficiently resistant to the stored liquids.
The collection capacity only applies to liquids. Empty, uncleaned packaging does not count. The collection facility may also be realized in storage. The choice of location for the collection facility may depend on the hazardous liquids stored. Kruizinga.nl is not liable for the type of use!
Please note! Any form of modification is not allowed. If this is the case, all regulations will lapse.
Reviews
8 out of 10, 1 reviews
5 stars
0 reviews
4 stars
1 reviews
3 stars
0 reviews
2 stars
0 reviews
1 star
0 reviews
8 out of 10
Both the product and the delivery were fulfilled as desired
Zowel het product als de levering zijn naar wens ingevuld
Automatically translated from Dutch ·
02-12-2024
This item is often ordered in combination with